Customization: | Available |
---|---|
Application: | Electronic, Instrument, Lighting |
Type: | Current Transformer |
Still deciding? Get samples of US$ 0/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Applicable conditions |
1, Environmental temperature: -20 ºC~70 ºC, relative humidity ≤ 85%; 2, Sea level: not exceeding 1000m; 3, Atmospheric conditions: There are no gases, vapors, chemical deposits, dust, or other corrosive or explosive media that seriously affect the insulation of the transformer. |
Technical requirements |
Comply with GB 1208-2006 "Current Transformers" standard and JB/T 10665-2066 "Micro Current Transformers" standard. |
Stuctural requirements |
The appearance is atmospheric and beautiful, the structure is novel and unique, the volume is small and the weight is light, the insulation and isolation ability is strong, and it is moisture-proof, anti-corrosion, and shockproof. |
Physical dimension: |
Parameter | Symbo | Range | Unit |
Rated input current | IPN | 100 | A |
Measuring current ranges | IP | 5~120 | A |
Secondary output | IO | 5 | A |
Accurate | X | 0.5 | |
Phase difference | δ | ≤120 | min |
voltage withstand | VD | 50Hz@rms/1min/>2.5 | KV |
Operating Frequency | f | 50/60 | HZ |
Insulation Resistance | VDR | DC500V/1min/>500 | MΩ |
Test error(Ta=25ºC±5): |
Current error ±% | Phase error ±′ |
Rated current | Rated current |
5A | 50A | 100A | Imax | 5A | 50A | 100A | Imax |
≤±0.75 | ≤±0.5 | ≤±0.5 | ≤±0.2 | ≤±120 | ≤±100 | ≤±90 | ≤±60 |
Mechanical parameters: |
Shell material | ABS flame retardant grade 94-V | Shell color | Black |
An input mode | Cable through core input | Magnetic core | Silicon Steel |
Two output mode | 1.5 square meters per red black line with a length of 2.0 meters |
Enameled wire | QA-1.2mm - 155 |
Medium filling material | Weight | ≤220g |