Type: | Hall Type |
---|---|
Output Signal Type: | Analog Output |
Production Process: | SemiConductor Integrated |
Material: | Plastic |
Accuracy Grade: | 0.5G |
Application: | DC Panel, UPS, Charging Equipment |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Electrical data:(Ta=25ºC,Vc=+5.0VDC) | ||||
Parmeter Ref |
CHB50E5S20 | CHB100E5S20 | CH150E5S20 | CHB200E5S20 |
Rated input Ipn(A) | 50 | 100 | 150 | 200 |
Measuring range Ip(A) | 0~+50 | 0~+100 | 0~+150 | 0~+200 |
Turns ratio Np/NS (T) | 1:2500 | 1:2000 | 1:3000 | 1:2000 |
Output current IS (mA) | +20*(IP/IPN) | +50*(IP/IPN) | +50*(IP/IPN) | +100*(IP/IPN) |
Secondary coil resistance RS(ohm) | 28 | 22 | 38 | 22 |
Inside resistance RM(ohm) | [(VC-1.5V)/(IS*0.001)]-RS | |||
Supply voltage VC(V) | +5.0 ±5% | |||
Accuracy XG(%) | @IPN,T=25°C < ±0.5 | |||
Offset current IOE(mA) | @IP=0,T=25°C < +0.2 | |||
Temperature variation of IOE IOT(mA/°C) | @IP=0,-40 ~ +85°C < ±0.005 |
|||
Linearity error εr(%FS) | < 0.1 | |||
Di/dt accurately followed(A/µs) | > 50 | |||
Response time tra(µs) | @90% of IPN < 1.0 | |||
Power consumption IC(mA) | 10+Is | |||
Bandwidth BW(KHZ) | @IPN DC-DC | |||
Insulation voltage Vd(KV) | @50/60Hz, 1min,AC 3.0 |
General data: | |
Parameter | Value |
Operating temperature TA(°C) | -40 ~ +85 |
Storage temperature TS(°C ) | -55~ +125 |
Mass M(g ) | 70 |
Plastic material | PBT G30/G15, UL94- V0; |
Standards | IEC60950-1:2001 |
EN50178:1998 | |
SJ20790-2000 |
Dimensions(mm): | ||
CHB-E5S20M | CHB-E5S20S | Connection |
General tolerance | ||
General tolerance:< ±0.5mm Primary through-hole: D20.5±0.15 Connection of Secondary : CHK-E5S20M: 2510-04A (Instead of Molex 5045-04A) CHK-E5S20S: 2EDG5.08-04P |
Suppliers with verified business licenses